RE: [External]OCR Maintenance Schedule
Michael Roberge 12 May 2023 14:33 UTC
Matt-
We used to do an annual oil sample and test the dielectric. Assuming it was good we used 64 operations or 3 years in service (whichever came first as our targets)-we mostly had type L reclosers. I am pretty sure this was developed from the Manufacturer recommendations. I know many Coops stretch the years out to match other maintenance cycles, but we tried to follow the factory recommendations.
TGIF!
-----Original Message-----
From: engineering@feca.simplelists.com <engineering@feca.simplelists.com> On Behalf Of Matthew Avery
Sent: Friday, May 12, 2023 5:46 AM
To: FECA-ENG ListServ <engineering@feca.simplelists.com>
Subject: [External]OCR Maintenance Schedule
This is an EXTERNAL email. Exercise caution. DO NOT open attachments or click links from unknown senders or unexpected email.
Good morning.
We are re-evaluating our OCR maintenance schedule. Currently, we replace all OCRs on an 8 year cycle.
What is your maintenance/replacement schedule?
Thanks,
J. Matthew Avery
SVP of Engineering & Operations
CHELCO